Floor-standing AC stations are self-contained climate control units engineered for large indoor spaces, commercial buildings, server rooms, event halls, and industrial facilities that require powerful cooling without the complexity of ducted systems. These units sit directly on the floor, deliver high volumes of conditioned air at low or medium static pressure, and are typically mounted on casters or leveling feet for flexible placement. Unlike portable spot coolers, floor-standing AC stations combine robust compressor technology, large evaporator and condenser coils, and advanced control electronics into a single cabinet. They are designed for continuous operation, rapid temperature pull-down, and precise humidity management. In demanding environments such as data centers, manufacturing floors, and temporary event structures, these stations provide a reliable alternative to central air conditioning when permanent HVAC infrastructure is unavailable or insufficient.
AMPPAL manufactures a comprehensive range of floor-standing AC stations with cooling capacities from 7 kW to 70 kW. Each unit integrates high-efficiency rotary or scroll compressors, environmentally friendly R410A or R32 refrigerant, and microprocessor-based controls. Below are the primary technical parameters across the standard product line.
The following table presents five representative AMPPAL floor-standing AC stations. These models cover the most common commercial and industrial cooling requirements. All specifications are verified at standard rating conditions: 27°C dry bulb / 19°C wet bulb indoor, 35°C dry bulb outdoor.
| Model | Cooling Capacity (kW) | Power Input (kW) | Airflow (m³/h) | Noise dB(A) | Dimensions W×D×H (mm) | Net Weight (kg) |
| FSAC-07 | 7.0 | 2.4 | 1,200 | 52 | 600×650×1,450 | 95 |
| FSAC-12 | 12.0 | 4.1 | 2,100 | 55 | 750×700×1,550 | 140 |
| FSAC-17 | 17.5 | 5.8 | 3,000 | 58 | 850×750×1,650 | 190 |
| FSAC-25 | 25.0 | 8.2 | 4,200 | 62 | 950×800×1,750 | 280 |
| FSAC-45 | 45.0 | 14.5 | 7,000 | 66 | 1,100×850×1,900 | 430 |
For higher capacity requirements, AMPPAL offers the FSAC-70 model with a cooling capacity of 70 kW, power input of 23.8 kW, airflow of 8,500 m³/h, and noise level of 68 dB(A). All models include hot gas bypass for low-ambient operation, high and low pressure switches, phase sequence protection, and crankcase heater as standard safety features.
Every AMPPAL floor-standing AC station comes with an advanced microprocessor controller that supports multi-language interface including English. The controller maintains precise temperature set points within ±1°C and relative humidity set points within ±5% RH. Key control features include:
Floor-standing AC stations require no permanent ductwork, making installation straightforward. Place the unit on a level surface with at least 500 mm clearance from the air inlet and 1,500 mm from the air outlet. Do not place objects directly in front of the condenser air discharge. For heat rejection, the unit discharges warm air through a flexible duct or louver. AMPPAL supplies a standard 300 mm diameter, 3 m long flexible duct for condenser exhaust; extension ducts are available in 5 m and 7.5 m lengths. Ensure the exhaust duct has no sharp bends exceeding 90 degrees to avoid static pressure loss above 50 Pa. Connect the unit to a dedicated electrical circuit with appropriate breaker and ground fault protection. For units above 17 kW, a lockable disconnect switch must be installed within sight of the unit.
Proper maintenance extends the service life of floor-standing AC stations beyond 15 years under normal operating conditions. Follow this recommended schedule:
| Component | Task | Frequency |
| Air filter | Wash with mild detergent and water, dry completely | Every 2 weeks or when airflow drops 10% |
| Evaporator and condenser coils | Inspect for dust and debris; vacuum or blow with compressed air | Monthly |
| Condensate drain pan | Clean and check for algae growth; use biocidal tablet if needed | Monthly |
| Condensate pump (if equipped) | Test float switch and check discharge line for obstruction | Every 3 months |
| Compressor electrical connections | Tighten terminals and check for overheating signs | Every 6 months |
| Refrigerant charge | Verify subcooling and superheat; check for leaks | Annually |
| Fan motors and bearings | Lubricate if applicable; check for abnormal noise | Annually |
Q: How do floor-standing AC stations differ from portable air conditioners?
A: Floor-standing AC stations are significantly more powerful and durable than portable air conditioners. A typical portable AC unit delivers 2–4 kW of cooling with airflow under 500 m³/h, while AMPPAL floor-standing AC stations start at 7 kW and reach 70 kW with airflow up to 8,500 m³/h. Floor-standing units use heavy-duty scroll or rotary compressors designed for 24/7 continuous operation, whereas portable units use lightweight reciprocating compressors that overheat under constant load. Floor-standing AC stations also include advanced controls such as Modbus RTU, phase protection, and hot gas bypass, which portable units lack. They are built with galvanized steel cabinets and industrial-grade fans, making them suitable for server rooms, warehouses, and production floors where portable units would fail within months.
Q: What exhaust duct length is recommended for hot air discharge?
A: For optimal performance, keep the exhaust duct as short and straight as possible. The standard length of 3 meters is recommended for units up to 17 kW. For every additional meter of duct length, static pressure increases by approximately 8 to 12 Pa depending on duct diameter and air velocity. AMPPAL floor-standing AC stations are rated for a maximum external static pressure of 150 Pa. If you need to run the duct 5 meters or longer, increase the duct diameter from 300 mm to 400 mm and avoid more than two 90-degree bends. Exceeding the maximum static pressure will reduce condenser airflow, raise head pressure, and trigger the high-pressure safety switch. Always use insulated duct material to prevent condensation dripping on the floor.
Q: Can floor-standing AC stations operate in low ambient conditions?
A: Yes. Standard AMPPAL floor-standing AC stations operate in cooling mode at outdoor ambient temperatures from 18°C to 45°C. For ambient temperatures below 18°C, select the low-ambient kit, which includes a head pressure control valve and variable-speed condenser fan. The low-ambient kit allows reliable operation down to -15°C. This is essential for server rooms in cold climates where cooling is still required even when outside air is freezing. The hot gas bypass system prevents evaporator coil freezing and maintains stable suction pressure. For outdoor installation in harsh environments, AMPPAL offers a weatherproof enclosure with heated compressor crankcase and anti-corrosion coating on all copper fins.
Q: What type of power supply do these units require?
A: Models from 7 kW to 12 kW operate on single-phase 208–240V AC at 60 Hz. Models from 17 kW and above require three-phase 380–480V AC at 60 Hz. A neutral conductor is not required for three-phase models. Each unit has a dedicated terminal block sized for the maximum running current plus 25% safety margin. For a 17.5 kW model with a power input of 5.8 kW, the running current at 400V three-phase is approximately 9.5 A, so a 16 A circuit breaker with type C curve is recommended. Voltage fluctuation must stay within ±10% of the rated voltage. Undervoltage below 342V on a 380V system will cause the compressor to draw excessive current and may trip the internal overload protector. AMPPAL provides an optional phase monitor that automatically shuts down the unit if phase loss or phase reversal occurs.
Q: How loud are floor-standing AC stations and can they be used in offices?
A: Noise levels range from 52 dB(A) for the 7 kW model to 68 dB(A) for the 45 kW model at 1 meter distance. For reference, a normal conversation is about 60 dB(A), and a busy open office is around 55–60 dB(A). The 7 kW AMPPAL FSAC-07 at 52 dB(A) is acceptable for small offices and meeting rooms. The 12 kW model at 55 dB(A) is suitable for retail spaces and restaurants. Larger units above 17 kW produce 58 dB(A) or more and are generally not recommended for occupied office areas unless placed in a mechanical room or behind an acoustic barrier. For noise-sensitive environments, AMPPAL offers a low-noise package with an additional 10 dB(A) reduction by using a larger, slower condenser fan, double-wall cabinet, and compressor sound blanket. This package increases the cabinet depth by 150 mm and adds about 8% to the unit cost.
Q: Do floor-standing AC stations also provide heating?
A: Standard cooling-only floor-standing AC stations do not provide heating. However, AMPPAL offers an optional reverse-cycle heat pump version for models from 7 kW to 25 kW. The heat pump model provides heating capacity approximately 10% higher than the cooling capacity. For example, the FSAC-12 heat pump delivers 13.2 kW of heating at 7°C outdoor ambient. Alternatively, an electric heater module rated at 3 kW, 6 kW, or 9 kW can be factory-installed inside the air discharge plenum. The electric heater operates independently of the compressor and can be used while the compressor is off, providing year-round climate control. All heating options include a dedicated high-limit thermal cutout and fan interlock to prevent operation without airflow.
Q: What maintenance is required for floor-standing AC stations?
A: Regular maintenance is essential to maintain efficiency and extend equipment life. Monthly tasks include cleaning the air filter, checking condenser coil cleanliness, and inspecting electrical connections. Every six months, the refrigerant pressure should be checked, fan motors inspected, and drain lines flushed. The scroll compressor requires no oil change under normal operating conditions and is rated for over 50,000 hours of operation. The condenser coil should be cleaned with compressed air or a soft brush when dust accumulation exceeds 1 mm, as dirty coils can reduce cooling capacity by 15–20%. AMPPAL units include a maintenance access panel and removable filters that allow technicians to complete routine service without moving the entire unit. The optional remote monitoring module can track compressor runtime, coil temperature, and fault history to support predictive maintenance.
Q: What refrigerants are used in AMPPAL floor-standing AC stations?
A: AMPPAL floor-standing AC stations use environmentally responsible refrigerants selected according to regional requirements. Standard models use R410A refrigerant, which has zero ozone depletion potential and excellent thermodynamic performance. Newer high-efficiency models can be configured with R32 refrigerant, which has a lower global warming potential compared with R410A. Refrigerant circuits are factory charged and sealed, requiring no refrigerant adjustment during installation under normal conditions. Each unit undergoes a factory leak test at 4.5 MPa pressure to ensure long-term reliability. For export markets with specific refrigerant regulations, AMPPAL can provide customized configurations to meet local environmental standards.
Q: Can these AC stations be integrated with building management systems?
A: Yes. AMPPAL floor-standing AC stations support integration with building management systems through Modbus RTU communication as standard. The communication interface allows monitoring of operating status, temperature settings, compressor operation, fan speed, and alarm conditions. Optional BACnet gateways are available for facilities using BACnet/IP networks. Remote control functions include start/stop commands, mode selection, temperature adjustment, and fault reset. This integration enables centralized management of multiple cooling units across data centers, industrial facilities, and commercial buildings. The communication protocol documentation and register maps are provided for system integrators during project implementation.
Q: Are AMPPAL floor-standing AC stations suitable for outdoor installation?
A: Standard units are designed for indoor installation. For outdoor applications, AMPPAL provides an outdoor enclosure option with IP54 protection, weatherproof sealing, and corrosion-resistant treatment. Outdoor configurations include additional insulation, rain protection, and enhanced electrical protection to withstand changing weather conditions. The operating temperature range remains -30°C to +50°C with proper configuration. Outdoor installation requires consideration of ventilation clearance, drainage, and protection from direct sunlight to maintain rated performance. AMPPAL technical engineers can review installation conditions and recommend suitable configurations for outdoor projects.
Q: How do I select the right floor-standing AC station model?
A: Model selection depends on several factors, including required cooling capacity, room size, heat load, airflow requirements, installation environment, and power availability. For example, a small electrical room with limited heat generation may require a 7 kW unit, while a large industrial workshop or data center may need multiple 25 kW or 45 kW units operating together. The heat load calculation should consider equipment heat output, personnel, lighting, and ambient temperature conditions. AMPPAL provides technical support to help customers select suitable models based on actual application requirements. Providing information such as room dimensions, heat sources, target temperature, and installation conditions will help ensure the correct AC station configuration.
AMPPAL understands that no two installations are identical. Beyond the standard floor-standing AC stations, the company offers a full range of factory-installed options. These include:
Every custom order is reviewed by an AMPPAL application engineer to ensure the final configuration meets local electrical codes and performance expectations. Standard lead time for custom features is 3 to 4 weeks, while standard models ship from stock within 5 business days.